Quick Answer

AC running but not cooling usually comes down to one of five things: a clogged air filter, a frozen evaporator coil, low refrigerant, a failed capacitor, or dirty condenser coils. Start with the filter — it causes more than half of these calls and takes 30 seconds to check.

You get the call. Tenant says the AC's been running all night and the apartment's still 82 degrees. The unit is clearly on — fan's blowing, compressor's humming — but no cold air. Before you start pulling things apart, run through this flow. Every step eliminates the most common cause at that point.

The 5 Most Common Causes of AC Not Cooling

1

Dirty or clogged air filter

Restricts airflow across the evaporator coil, causing it to freeze or starve the system of heat exchange capacity. Most common cause. Check first, always.

2

Frozen evaporator coil

Ice on the indoor coil blocks airflow completely. Usually caused by a dirty filter, blocked return vents, or low refrigerant. Visual check on the air handler tells you immediately.

3

Low refrigerant (leak)

System doesn't have enough refrigerant to absorb heat. You'll see ice on the suction line, hear hissing or bubbling, and notice the system runs constantly without reaching setpoint.

4

Faulty start or run capacitor

Compressor hums but doesn't start, or the condenser fan runs erratically. Capacitor fails due to heat and age. Common on units over 5 years old in hot climates.

5

Dirty condenser coils (outdoor unit)

Can't reject heat. The system works harder, runs hotter, and loses cooling capacity. Check the outdoor coil — if it's caked with debris, the whole system is working against itself.

The Diagnostic Flow — Work Through These in Order

Don't skip ahead. Each step eliminates the cheap problems before you start looking at the expensive ones.

1

Check the Air Filter

Pull the filter and hold it up to the light. If you can't see through it, it's the problem. A filter clogged past its service life cuts airflow enough that the evaporator coil drops below freezing and ices over, blocking the remaining airflow entirely.

Replace it. If the coil is frozen (Step 2), you need to defrost first — but the filter check comes first because you need to know whether to fix the cause before you defrost.

Manufacturer note: Most residential systems (Carrier, Lennox, Trane, Rheem) recommend 1” filters changed every 30–90 days depending on occupancy and pet load. MERV 13+ filters can starve lower-static systems — check your system's fan specifications before upsizing filter efficiency.
2

Check for a Frozen Evaporator Coil

Open the air handler access panel. The evaporator coil should look dry and clean. If you see ice or heavy frost — on the coil itself or on the large copper suction line going into the air handler — the coil is frozen.

A frozen coil is a symptom, not a root cause. The root cause is either the dirty filter you just found, blocked return vents, or low refrigerant (Step 4). To clear it:

  • Turn the system to Fan Only (heat and cool off) for 2–4 hours
  • Do not run cooling while the coil is frozen — you will damage the compressor
  • Once defrosted and the filter is replaced, restart and monitor for re-freeze
Do not skip this step. Running the compressor against a frozen coil causes liquid refrigerant slugging — it can destroy the compressor in under an hour. If the coil re-freezes after defrost with a clean filter, move to refrigerant check.
3

Check the Outdoor Unit (Condenser)

Go outside to the condenser unit. You're looking for three things:

  • Is the fan running? Fan spins, compressor hums but doesn't cool — suspect capacitor (Step 4). Fan not running at all — check breaker and capacitor.
  • Are the coils caked with debris? Dirt, cottonwood, grass clippings on the outside of the condenser fins cut heat rejection dramatically. A garden hose rinse from inside out (not outside in) can restore significant capacity.
  • Is there ice on the suction line? The large insulated copper line going into the unit — ice here confirms the refrigerant is too cold, indicating low charge or restricted airflow.
Pro tip: Check that the disconnect box near the outdoor unit is fully engaged. Vibration can loosen the fuse block over time, causing intermittent or no power to the compressor.
4

Test the Capacitor

If the condenser fan is running but the compressor is humming and not starting (or starting and quickly shutting off on thermal overload), the capacitor is the first thing to check. Capacitors are the most common component failure on residential AC units.

To test:

  • Shut off power at the disconnect box
  • Wait 5 minutes for the capacitor to discharge (do not skip this — they hold lethal charge)
  • Use a multimeter with a capacitance setting to test against the MFD rating printed on the capacitor
  • Acceptable range is typically ±6% of rated MFD. Below that, replace it.

Capacitors are typically $15–40 in parts and a 15-minute swap. They're marked with dual ratings (e.g., 45/5 MFD) — the higher value is for the compressor, lower for the fan motor.

Manufacturer specs: Carrier, York, and Goodman units use capacitors rated to specific MFD and voltage. Always match or exceed voltage rating (a 370V capacitor can replace a 370V spec; use 440V for a 440V spec). Never substitute a lower voltage rating.
5

Check Refrigerant Charge (Requires Gauges & EPA 608)

If you've cleared the filter, the coil isn't frozen (or re-freezes after defrost), the capacitor is good, and the condenser coils are clean — you're likely looking at a refrigerant issue.

Signs that point to low refrigerant:

  • System runs continuously without reaching setpoint
  • Suction line ice or frost after defrost with clean filter
  • Hissing or bubbling sound near the refrigerant lines
  • Supply air temperature is only a few degrees below return air temp (healthy delta-T should be 14–22°F across the coil)

Refrigerant diagnosis requires manifold gauges. If you're not EPA 608 certified, this is where you hand off to a licensed tech. Adding refrigerant without finding the leak is a temporary fix — the refrigerant will leak out again.

R-22 systems: If you're on a pre-2010 system still running R-22, refrigerant costs have increased significantly and this may be the conversation to start about system replacement. Most R-22 systems are past their 15-year design life at this point.

When You Need to Call a Licensed HVAC Tech

Stop and call in if:

  • The coil re-freezes after defrost with a clean filter and clear return vents
  • You hear hissing, gurgling, or bubbling from refrigerant lines
  • The compressor won't start even with a new capacitor
  • You measure supply air temp within 5°F of return air temp (no delta-T)
  • The unit is tripping a breaker repeatedly

Everything above that point — filter, frozen coil, capacitor, dirty condenser — is maintenance-level work. Refrigerant handling, compressor diagnosis, and electrical troubleshooting beyond the capacitor is licensed HVAC territory.

FixAtlas

This is the same diagnostic flow FixAtlas walks you through — on every call.

FixAtlas gives maintenance techs and property managers structured troubleshooting workflows, manufacturer-backed data, and real-world repair guidance for HVAC, plumbing, electrical, and appliances. Free during early access.

Get Free Early Access →